Incineration of biomedical waste

– intended to destroy and without polluting the environment, biomedical anatomical solid
and non-anatomical waste
‑ Smoke burning incinerator with a total volume of combustion chamber of approximately
1 m3 (± 10%), with manual waste 
loading via a front door with an inspection flap (to check the flame)  eliminatory
‑  First combustion Chamber: more than 60% of the total volume
‑  Post combustion Chamber (burning of smoke): Up to 40% of the total volume
‑ Interior lining of chambers made of refractory material (nature to be indicated) making it
possible to reach and maintain a temperature up to 1000 °C eliminatory
– Forced air Convection (by motorised Fan kW maximum) eliminatory
– automatic cycle of maintaining the working temperature (burner control)
– Insulating Layer (nature of the materials to indicate) between the combustion chamber
and the exterior metal structure, including loading door (less than 60 °C on the frame in a
normal regime), heat resistant layers of external protection 

– Calorific power required: 
115 to 150 kW (418,000 to 543 400 kJh-1)
– automatic illumination burners (electrical or piezoelectric) with security of flame
presence eliminatory
– heating oil supply (diesel): 
8 litres/hour maximum
– Fuel Injection pump for 1 kW maximum
– autonomy Tank of approx. 150 litres fitted with a booster pump
– An expansion chamber provided with an ambient air intake flap located in the flue/burnt
gases path reduces the gas ejection velocity and dilutes it
– The discharge into the atmosphere should be free of the following (results certified by a
monitoring body acceptable by the purchaser): carbon monoxide (CO <0.1%), 
nitrogen oxides (Nox) and carbon (<8%), unburned fuel and hydrocarbons (<0.3 ‰), solid
particles (<7%).
– Front or side control box comprising:
     * on switch
     * Getting started
      * Emergency stop
      * Choice of cycle (manual or automatic)
      * Choice of working temperature
      * Choice of cycle time
      * Ventilation
      * Priming of burners
* Operation and phase indication indicators (presence of flame, temperature, time, fan, end
of cycle, fault alarms, on / off, …)
Safety devices :
– Flame presence security: stop and alarm after several unsuccessful attempts to spark
Eliminatory
– overheating safety: fuel cutoff in the event of excess temperature Eliminatory
– Security all closed doors (except possible inspection door)
– Fuse protection
– Disconnector to completely isolate the device during maintenance. 
Spare parts to provide:
– 01 door seal
– 01 set all of the light indicators
– 01 set of all thermocouples
– 02 sets of the nozzles of the burners
– 01 set of ignition systems of the flames
– 01 set of coils of all switches
– 01 set of coils of all solenoid valves
– 01 replacement kit for the fuel injection pump 
– 02 sets of all protection fuses
Each equipment will be supplied with:
– the local 
– 01 fireplace 
– 01 ash tray with a displacement scraper
– 01 kit for cleaning the nozzles of the burners
– 01 adapted manual igniter (in case of automatic ignition failure)
– Electrical box for mains connection with at least one modular circuit breaker of suitable
size
– 02 powder fire extinguishers (with their wall hangers)
– 01 maintenance kit
-1 UPS of adequate power
-1 voltage stabilizer with recovery  time 
– All the other accessories necessary for the proper functioning of the equipment
– 01 user and maintenance manual in French